IFT258 Automatic Burner Control Unit

IFT258 Automatic Burner Control Unit
Product Detailed
Related Categories:Auto Ignition System
Protection grade: IP40 Germany technology autburner running.omatic burner controller can be directly used to start and detec

Technical indexes:

1. Power supply: AC220V plus-minus 10% 50Hz.

2. Ambient temperature: Minus 20 celsius degree to 65 celsius degree without condensation.

3. Flame detection current: Adjustable between 2-20 microamp.

4. Protection grade: IP40.

5. Ignition cable: Less than 5m (temperature resisting high-voltage line).

6. Cable length: For electrode ionized detection mode: Max 75m; For UV detection mode 100m.

Detecting mode: Both ignition and detection functions are combined into one electrode or two of the electrode separated control.

Attentions:

1. The power cord shall be fixed, and live wire L and zero line N shall not be connected error in order to prevent equipment damage.

2. The solenoid valve and ignition transformer shall be driven by AC220V power source, with max. Output currrent 2A and each output current no greater than 2.5A.

3. Combustion indicator contact(terminals 13-14) and ignition failure signal contact (terminals 8-9): Max. Current 2A, max. Voltage: 253V.

4. Max. Working voltage of UV flame detector: 230V, without internal fuse.

5. An independent detection cable is used and in the protection of plastic cable pipe, shall be separated from the main cable in case of remote control, to prevent electromagnetic interference.

6. In case of UV detector, the 7# terminal may not be earthed.

7. Terminals 11 and 12 have been parallel connected inside it.

8. Installation: 35mm U-shaped rail can be used, width 113mm, height 75mm and depth 120mm, distance of two installation holes on the base plate.

9. When a signal electrode is used, the 7# terminal of the burner and controller must be earthed in order to prevent equipment damage.

10. Before power supply, the two fixation screws on the automatic burner controller must be screwed down.

11. The secondary ignition operation shall be done in 20 seconds after the alarm red light is on, to prevent overload damage.